Product Description

Wireless universal mixing valve controller for heating or cooling zone control. The controller receives heat demand signals (RF 868,3 MHz)from thermostats CM67RFMV or CM67z.
The CM67RFMV also provides parameter settings for: minimum water temperature setpoint, mixing valve runtime, pump after running ime and heating or cooling operation mode.

Technical Properties

Product description Universal mixing valve controller
Control functions room temperature control; water temperature control (optional)
Manual operation functions push buttons for valve open/close
ErP Class V
Control output signal
  • 2x 230 V (3 A) on relay contacts for mixing valve open/close (not potential free contacts!)
  • 230 V (3 A) on relay contact for pump on/off (not a potential free contact!)
RF communication distance 30 m
Blocking immunity Receiver class 2 (ETSI EN300220-1 version 1.3.1)
LED functions mixing valve open/close: red/green; pump on: green; and several error messages: red
Housing (HxWxD) 161.5 mm | 121 mm | 46 mm
Mounting DIN-rail or wall
Protection class IP54
Power supply 230 V;50Hz | max. 1380 VA