Skip Ribbon Commands
Skip to main content

V5005TY20251000

V5005TY20251000

The V5005T Kombi-FCU is a Pressure Independent Control Valve (PICV)...

Product Description

The V5005T Kombi-FCU is a Pressure Independent Control Valve (PICV). It combines a flow controller and a full stroke, full authority temperature controller in one valve. Equipped with an actuator Kombi-FCU provides a full stroke modulating temperature control. It is suitable for use in variable and constant flow systems. They may be used as constant flow limiter in constant flow systems (without an actuator) or as a Pressure Independent Control Valve in variable flow systems.

V5005T Kombi-FCU is typically used for balancing and temperature control of fan coil units, chilled ceilings and one-pipe heating systems.

  • Automatic pressure independent balancing and control
  • Precise pressure independent flow performance
  • Highest energy saving potential due to efficient energy transfer and minimized pump speed
  • Measuring possibility to find the optimal setpoint for the pump
  • Versions with or without measuring connections available
  • Reduced movements of actuators as pressure fluctuations do not influence the required temperature
  • No complex calculation needed for selection
  • No balancing method needed for commissioning
  • Wide range of application
  • Sizes DN15 to DN25 cover all popular sizes on FCUs
  • Various versions to support standard flow rates as well as low flow and high flow needs
  • Covers hydronic balancing and temperature control in one valve thus reducing mounting costs
  • Easy commissioning
  • Presetting with visual flow scale indicating directly the preset liters per hour
  • Pre-setting by hand without the need of tools
  • Can balance a system even if only parts of a building are in operation
  • Maintenance friendly
  • Emergency shutoff function with plastic cap - not for permanent use
  • Measuring possibility for problematic applications (only with versions having measuring connections)
  • Dirt resistant no dead zones in the valves. Continuous flow assures self cleaning effects

Technical Properties

Medium type water or water-glycol mixture according to VDI 2035
Delta-P 15 ... 400 kPa
DN size 25 mm
Minimum flow 100 l/h
Port connection internal threads
Maximum flow (qs) 1000 l/h
Connection of accessories side connections
Max. delta P 400 kPa
Pre-setting Yes
Media temp. -10 ... 120 oC
Place in installation return
Valve Control function Pressure Independent PICV
Automatic balancing support Yes
Additional Descriptions

Leakage: According to Class IV IEC 60534-2-3 (up to 3.5 bar differential pressure), According to Class III IEC 60534-2-3 (up to 4 bar differential pressure) 

More Information http://www.hydronic-balancing.info/home-en.html
Port diameter Rp 1 inch