Mounting |
directly on wall or wall-box |
Protection class |
IP30 |
Manual operation functions |
room setpoint; fan speed on/off, low/med/high or auto; heat/cool change-over manual or auto |
Input signal |
optional remote room sensor, water sensor, setback contact for energy saving |
Temp. setpoint range |
10 ... 32 oC |
Control output signal |
switches (230V 1A inrush 3A) on/off for heating- and cooling valve, switches (230V 3A inrush 6A)for fan (3-speed) and heater |
Display functions |
setpoint temperature, room temperature, mode of operation: heat, cool or standby |
Power supply |
230 Vac | 5 VA |
Housing (HxWxD) |
97 mm | 148 mm | 29 mm |
Terminal max. wire size |
2,5 mm2 |
Product literature language |
controller supplied with installation instructions in English, French, Italian, Spanish |
Additional Descriptions |
- Installer Set Up routine for application selection and parameter settings
- parameter settings retained in event of power loss
- adjustable dead band for heat/cool sequence operation
- activity sensing: back to energy saving mode if no button is pressed for a selected period of time
- freeze protection
- LCD display with bright backlight
- keypad lockout (total or partial)
|
Product description |
Fan Coil controller, for 2-pipe systems only |