Skip Ribbon Commands
Skip to main content
​This extension for Google Chrome will allow you to click on the links in the PDF CAD files and open the related documents from your browser.

Series CVC, HLE - Hot gas bypass valves with fixed orifice, internal pressure equalisation and adjustable suction pre

Series CVC, HLE - Hot gas bypass valves with fixed orifice, internal pressure equalisation and adjustable suction pre

Series CVC, HLE Hot gas bypass valves with fixed orifice, internal pressure equalisation and adjustable suction pressure limitation.

Product Description

Series CVC, HLE Hot gas bypass valves with fixed orifice, internal pressure equalisation and adjustable suction pressure limitation.
Hot gas bypass valves series CVC and HLE are used to adjust the compressor capacity to the actual evaporator capacity in a refrigerating plant. The hot gas bypass valve can be installed in a bypass tube between the hot gas line and suction line. The suction pressure is downward limited by flowing hot gas from the high pressure to the low pressure side. For plants in general refrigeration and for original equipment such as dehumidifiers, air driers, water coolers or ice-making machines.
  • Smallest dimensions
  • High performance
  • Hermetic construction
  • Adjustable suction pressure limitation
  • Extreme durability thanks to welded stainless steel head and stainless steel diaphragm
  • Special versions (bypass, other refrigerants, etc.) on request
  • For capacities of orifices download attached engineering manual or check with our selection software Valve Tool

Technical Properties

Series CVC
Orifice solid built-in
Connections solder
Pressure equalizer internal
Balanced port no
Brass parts body
Stainless steel parts internals, power head
Copper parts connection tube
Max. ambient temperature 100 oC
Max. pressure PS 25,5 bar
Max. test pressure 28 bar
Thermal charge all CFC, HCFC, HFC, not for ammonia
Technical literature Download PDF with Series number in Table

Produse

Product Type Orifice size
Inlet ODF
Outlet ODF
Adjusting range
Factory setting
CVC

_CVC

CVC-Y29110
4 6mm 12mm 1 ... 6 bar 3,2 bar

CVC-Y29210
4 1/4" 1/2" 1 ... 6 bar 3,2 bar
HLE

HLE-00002
4,5S 3/8" 1/2" 1 ... 9 bar 3,5 bar