The V5001P Kombi-Auto differential pressure control valve is used to maintain automatically a hydronic balance in residential or commercial hydroni...

Product Description

The V5001P Kombi-Auto differential pressure control valve is used to maintain automatically a hydronic balance in residential or commercial hydronic heating and cooling systems. It shall be installed in the return pipeline. It is used in systems with variable volume flows, for example two-pipe heating systems, and creates a hydronic balance by keeping differential pressure over consumers at a constant preset level even under changing flow or pump pressure conditions, for example in part load states. Hydronic balance is a significant requirement for efficient opera-tion of a hydronic system. In an unbalanced system under- or oversupply of energy to individual circuits or heat exchangers can occur. Apart from correct selection of radiator valves, regulation of individual circuits is necessary and in some countries required by national standards or regulations.

  • Automatic balancing of differential pressure
  • Highest energy saving potential due to efficient energy transfer and minimised pump speed
  • Lower noise emission on control valves
  • High authority over the control valves
  • Dividing systems into pressure independent zones
  • No complex calculation needed for selection
  • No balancing method needed for commissioning
  • Wide range of application
  • Sizes DN15 up to DN50
  • Wide pre-setting ranges
  • Very high flow rates
  • Easy commissioning
  • Pre-setting with visual delta-p-scale in kPa
  • Pre-setting by hand without the need of tools
  • Pre-setting lead sealable
  • Removable insert for installation in tight spaces
  • Insulation shells up to DN50 included
  • Maintenance friendly
  • Concealed shut-off function up to DN50
  • Various measuring possibilities for problematic applications

Technical Properties

Medium type water or water-glycol mixture according to VDI 2035
Delta-P 30 ... 60 kPa
DN size 40 mm
Minimum flow 250 l/h
Port connection internal threads
Maximum flow (qs) 13000 l/h
Connection of accessories side connections
Nominal pressure PN16
Pre-setting Yes
Media temp. -20 ... 130 oC
Kvs value 24,5
Materials

Valve housing made of dezincification resistant brass, Blind stops made of brass, Valve insert made of brass and stainless steel, Handwheel assembly made of plastic and brass, SafeConTM pressure test valve made of brass

Place in installation return
Valve Control function Differential Pressure DPCV
Automatic balancing support Yes
Port diameter Rp 1 1/2 inch