Product Description
The V5032 Kombi-2-plus is a static, variable orifice double-regulating balancing valve for the return with additional shutoff function.
- It is suitable for use in variable and constant flow systems to manually balance the flow and to set resistances to an equal level all over the system.
- V5032 Kombi-2-plus is typically used for static balancing of fan coil units, air handling units, chilled ceilings and two-pipe heating systems. A usage in the return is to be preferred but it can be used also in the supply.
Technical Properties
Medium type |
water or water-glycol mixture according to VDI 2035 |
DN size |
50 mm |
Port connection |
internal threads |
Connection of accessories |
spindle / side connections |
Nominal pressure |
PN16 |
Pre-setting |
Yes |
Media temp. |
-20 ... 130 oC |
Kvs value |
41.5 |
Body pattern |
Y-pattern |
Materials |
- V5032...BLF Kombi-2-plus (DN15): Valve housing with internal threads to DIN EN 10226-1 for threaded pipe and two G1/4 connections equipped with SafeConTM pressure test valves; Handwheel for the shut-off function; Pre-setting and display; Two SafeConTM measuring connections; Installation and setup instructions
- V5032...B Kombi-2-plus (DN15 - DN50): Valve housing with internal threads to DIN EN 10226-1 for threaded pipe and two G1/4 connections equipped with SafeConTM pressure test valves; Valve insert with shutoff function; Handwheel with pre-setting dial and display; Two SafeConTM measuring Connections; Installation and setup instructions
- V5032...B Kombi-2-plus (DN65 - DN80): Valve housing with internal threads to DIN EN 10226-1 for threaded pipe and two G1/4 connections equipped with SafeConTM pressure test valves; Valve insert with shutoff function; Handwheel with pre-setting dial and display; Two SafeConTM measuring connections; Installation and setup instructions
|
Place in installation |
return |
Position indication |
Numeric display of pre-setting value. |
Measuring support |
Yes |
Valve Control function |
Double Regulating, static balancing DRV |
Automatic balancing support |
No |
Draining/filling support |
Yes |
Additional Descriptions |
- Manual balancing of flowrates
- Precise pre-setting with numeric scale
- Concealed pre-setting prevents unwanted operation
- Wide range of application
- Sizes DN15 up to DN80
- Versions for standard and low flow rates available
- Fast and safe measurement with SafeConTM measuring Connections 6 times faster than standard Binder connections
- DN size and settings readable on handwheel even with insulated valve
- All functions located on one side for easier access and use
- Optimal measuring in combination with Honeywell BasicMess (VM242) - all flow values are already included in the measuring device
- Maintenance friendly
- Insert fully interchangeable
- Integrated shutoff function
- Pre-setting is not changed during shutoff
|
More Information |
http://www.hydronic-balancing.info/home-en.html |
Additional description |
for water-glycol mixtures - max temperature 110C |
Port diameter |
Rp 2 inch |