District heating, direct heating circuit, DHW (Hy0502)

District heating, direct heating circuit, DHW (Hy0502)
  • Demand based control of remote energy transfer stations after target value request of downstream control circuits
  • Outdoor temperature-compensated flow temperature control for radiators and convectors
  • One heating circuit
  • Hot water preparation for tanks with internal heat exchanger

Unmixed heating1 circuit
Domestic Hot Water1 pump
Circ. pump1
District heating1 valve

Functions
  • The basic functions are contained in an indestructible program.
  • All the parameters are predefined with sensible basic settings and allow individual adjustments as necessary. PCs are not required for this.
  • All the relay outputs can be tested manually.
Remote energy control
  • Functions according to AGFW guidelines
  • Demand control of setpoint request from downstream control circuits
  • Sliding or fixed maximum limitation of the remote energy return temperature
  • Minimum valve stroke for exact recording of heat volume in low-load operation
  • Interval rinse for temperature recording in the primary return with closed remote energy valve
  • Fixed maximum limitation of the remote energy return temperature during hot water filling
Heating circuit
  • Time switch for daily, weekly and holiday programs for each heating circuit
  • Minimum/maximum limit of flow temperature
  • Frost protection function
  • Optimisation of switch-on times
  • Pump switching on demand
  • Forced pump running
Hot water control
  • Timer switch with daily and weekly program for tank filling and circulation pump
  • Anti-legionella automatic system
  • Hot water priority circuit, -Conditional priority, -Priority operation with intermediate heating
Combination
  • Combination option of up to five freely-selectable SMILE controllers
Communication
  • Communication takes place over the system bus without additional interfaces
  • Distance (max. 100 m)
  • Remote operation with the wall modules SDW.. also takes place using the system bus
Fault message
  • If the required temperatures cannot be achieved within a reasonable time, or sensors interrupt or short-out, then the controller will generate a fault message.

Related Parts

Product Type Description
Application for Smile digital controller

_Hy0502
Microprocessor controller district heating

SDC7-21WM
With connection base for wall installation

SDC7-21PM
With connectable terminal strips for control panel installation
Sensors

AF20-B65
Outside air temperature sensor

SF20-B54
Contact temperature sensor WF, VFB (2)

KTF20-65-2M
Hot water temperature sensor (without well) SF
Recommended

SDW10WE
Remote control with temperature selector/sensor and mode switch

SF20-B54
Return temperature sensor RLF
Selectable

VF20-1B54NW
Immersion temperature sensor (instead of SF20-B54)

VF20-3B54NW
Hot water sensor with NIRO immersion well (instead of KTF20-65-2M)

SDW30
Easy-to-use remote operation with display and complete programming unit along with temperature sensor/selector (instead of SDW10)

SCS-12
Base for Smile Controller, for control panel installation as touch protection

SWS-12
Connecting base for wall installation of SMILE panel models

SRR
Reducing attachment frame for control panel installation, assuming available control panel cut-out on controllers ZG52 /53 /55 / 82 /85 or ZG215 /215V /252 /254
Thermostat (selection according to specifications of the district heating company or DIN 4747/1)

STW+TR
Safety limiting thermostat STW