Product Description
According EN 806-2 pressure reducing valves of this type protect household water installations against excessive pressure from the supply. They can also be used for industrial or commercial applications within the range of their specification. By installing a pressure reducing valve, pressurisation damage is avoided and water consumption is reduced. The set pressure is also maintained constant, even when there is wide inlet pressure fluctuation. Reduction of the operating pressure and maintaining it at a constant level minimizes flow noise in the installation.
Technical Properties
Approvals |
- DVGW
- WRAS approval up to 23 oC
- KIWA (DN65 - DN100)
- SVGW
|
Medium type |
drinking water |
DN size |
80 mm |
Port connection |
flanges |
Nominal pressure |
PN16 |
Outlet pressure |
1.5 ... 7.5 bar |
Media temp. limit |
according to EN1567: 30 oC |
Flow capacity Kvs |
51 |
Body material |
ductile cast iron |
Body finishing |
powder coating |
Spring bonnet material |
ductile cast iron |
Balanced seat design |
Yes |
Additional Descriptions |
- LEAD FREE: Pb content of all materials less than 0.1 %
- Inlet pressure balancing - no influence on outlet pressure by fluctuating inlet pressure
- Patented cartridge solution for easy assembly and maintenance
- Three cartridge inserts for all nominal widths make warehousing efficient
- High corrosion resistance due to stainless steel cartridge and PA coating
- The adjustment spring is not in contact with the drinking water
- With inlet and outlet pressure gauge
- Functionality and performance have been confirmed by an accelerated life test with over 400,000 cycles (requirement acc. to EN 1567: 200,000 cycles)
- Conforms to BSEN 1567
- All materials are UBA conform
- ACS certified
|
Port diameter |
3 inch |
Maximum inlet pressure |
16 bar |
Minimum pressure drop |
1 bar |
Max. media temperature |
65 oC |