Skip Ribbon Commands
Skip to main content

V5032Y0050B

V5032Y0050B

Kombi-2-Plus Balancing Valve, Partner valve for V5001PY, for connection of included impulse tube, to extend measuring possibilities and to do a mass flow limitation on supply side, DN50

Product Description

The V5032 Kombi-2-plus is a static, variable orifice double-regulating balancing valve for the return with additional shutoff function.

  • It is suitable for use in variable and constant flow systems to manually balance the flow and to set resistances to an equal level all over the system.
  • V5032 Kombi-2-plus is typically used for static balancing of fan coil units, air handling units, chilled ceilings and two-pipe heating systems. A usage in the return is to be preferred but it can be used also in the supply.

Technical Properties

Medium type water or water-glycol mixture according to VDI 2035
DN size 50 mm
Port connection internal threads
Connection of accessories spindle / side connections
Nominal pressure PN16
Pre-setting Yes
Media temp. -20 ... 130 oC
Kvs value 41.5
Body pattern Y-pattern
Materials
  • V5032...BLF Kombi-2-plus (DN15): Valve housing with internal threads to DIN EN 10226-1 for threaded pipe and two G1/4 connections equipped with SafeConTM pressure test valves; Handwheel for the shut-off function; Pre-setting and display; Two SafeConTM measuring connections; Installation and setup instructions
  • V5032...B Kombi-2-plus (DN15 - DN50): Valve housing with internal threads to DIN EN 10226-1 for threaded pipe and two G1/4 connections equipped with SafeConTM pressure test valves; Valve insert with shutoff function; Handwheel with pre-setting dial and display; Two SafeConTM measuring Connections; Installation and setup instructions
  • V5032...B Kombi-2-plus (DN65 - DN80): Valve housing with internal threads to DIN EN 10226-1 for threaded pipe and two G1/4 connections equipped with SafeConTM pressure test valves; Valve insert with shutoff function; Handwheel with pre-setting dial and display; Two SafeConTM measuring connections; Installation and setup instructions
Place in installation return
Position indication Numeric display of pre-setting value.
Measuring support Yes
Valve Control function Double Regulating, static balancing DRV
Automatic balancing support No
Draining/filling support Yes
Additional Descriptions
  • Manual balancing of flowrates
  • Precise pre-setting with numeric scale
  • Concealed pre-setting prevents unwanted operation
  • Wide range of application
  • Sizes DN15 up to DN80
  • Versions for standard and low flow rates available
  • Fast and safe measurement with SafeConTM measuring Connections 6 times faster than standard Binder connections
  • DN size and settings readable on handwheel even with insulated valve
  • All functions located on one side for easier access and use
  • Optimal measuring in combination with Honeywell BasicMess (VM242) - all flow values are already included in the measuring device
  • Maintenance friendly
  • Insert fully interchangeable
  • Integrated shutoff function
  • Pre-setting is not changed during shutoff
More Information http://www.hydronic-balancing.info/home-en.html
Additional description for water-glycol mixtures - max temperature 110C
Port diameter Rp 2 inch