BA295I-1/2A

BA295I-1/2A

Backflow preventers of this type are suitable for the protection of drinking water systems against back pressure...

Product Description

Backflow preventers of this type are suitable for the protection of drinking water systems against back pressure, back flow and back syphonage. They can be used for residential buildings, industrial and commercial purposes within the scope of their specification. Fluids up to and including liquid category 4 to EN 1717 are protected.

Technical Properties

Approvals
  • DVGW
  • KIWA
  • BELGAQUA
  • SVGW
Media

Drinking Water

Liquid category (EN1717) class 4
DN size 50 mm
Port connection external threads
Port diameter 1/2 inch
Mounting position horizontal
Minimum inlet pressure 1.5 bar
Max. media temperature 65 oC
Body material stainless steel
Additional Descriptions
  • LEAD FREE: Pb content of all materials less than 0.1 %
  • Stainless steel construction
  • Optimal protection of the drinking water supply system
  • Integrated inlet strainer
  • Inlet check valve and discharge valve are combined in one cartridge
  • Minimal maintenance required, because the valve cartridge is completely replaceable
  • Optimized design prevents water Stagnation in normal operation
  • Easy access to all internal components
  • Low pressure loss and high flow rate
  • ACS certified
  • All materials are KTW approved
  • Approved by TUEV for low noise, Group 1 without limitations
Maximum inlet pressure 10 bar