Product Description
The automatic bypass and differential pressure valve controls water flow in the heating circuit according to the water pressure across it and is used to maintain a minimum flow rate through the boiler and to limit circulation pressure when other water paths are closed. A bypass circuit must be installed if the Boiler manufacturer requires one, or specifies that a minimum flow rate has to be maintained whilst the Boiler is firing. The use of automatic bypass valves becomes particularly important when heating systems include large numbers of thermostatic radiator valves (TRVs) - whilst the TRVs are open the automatic bypass valve remains closed, however, as the TRVs start to close, the automatic bypass valve starts to open maintaining the required water flow through the boiler. Using an automatic bypass valve is also likely to reduce noise in systems caused by excess water velocities. It also helps to reduce the corrosion caused by flue gas condensation as the boiler return temperature is raised.
Technical Properties
Medium type |
water or water-glycol mixture according to VDI 2035 |
Port connection |
internal threads |
Maximum operating pressure |
3 bar |
Differential pressure setpoint range |
0.05 ... 0.5 bar |
Max. media temperature |
110 oC |
Materials |
Unpolished brass housing, brass fittings and valve disc, High-grade synthetic material spring bonnet, high-temperature resistant synthetic material display tube, stainless steel spring, EPDM seals |
Additional Descriptions |
- Maintain minimum flow through a boiler
- Minimizes flow noise
- Hinders boiler corrosion
- Differential pressure finely adjustable using the indicator scale integrated in metal housing
- Presetting accessible directly
- Setting value is in meters water column
- No external controls required
|
pH-range |
8 ... 9.5 |
Differential pressure setpoint fixed |
0.2 bar |